From Voice Video Services Policy STIG
Part of VVoIP 1221
Unified Capabilities (UC) users require different levels of capability depending upon command and control needs. Special-C2 decision makers requiring Flash or Flash Override precedence must have eight hours of continuous backup power at all times. C2 users requiring Immediate or Priority precedence must have two hours of continuous backup power.
Inspect the VVoIP system design for evidence of continuous backup power to the infrastructure and command and control (C2) users. Ensure a UPS system is provided for all parts of the VVoIP infrastructure, including the core LSC/MFSS, adjunct systems providing critical services, SBC, CER, LAN elements, and endpoints as follows: - All VVoIP system devices including portions of the LAN that directly support one or more special-C2 users are minimally provided 8 hours UPS. - All special-C2 user VVoIP endpoints relying on Power over Ethernet (PoE) must have power sourcing equipment (PSE) sized to support the asset and endpoints by the UPS for a minimum 8 hours. - All special-C2 user VVoIP endpoints without PoE must be minimally provided 8 hours UPS. - UPS systems (battery at a minimum; plus optional generator) supplying infrastructure power supporting special-C2 and C2 users must also support environmental power (HVAC) such that equipment failures are prevented. - In no case should a UPS system immediately, or within a short time, drop power to the supported equipment when primary power is removed. This would indicate an undersized or defective UPS unit. Determine if the infrastructure assets being reviewed directly support one or more special-C2 user. If no special-C2 users are supported, this requirement is not applicable. If special-C2 users are supported, determine if assets are provided with 8 hours of backup power. If 8 hours of backup power is not provided for LAN Infrastructure, WAN boundary, VVoIP infrastructure, and VVoIP endpoints to support special-C2 users, this is a finding.
Ensure a UPS system is provided for all parts of the VVoIP infrastructure, including the core LSC/MFSS, adjunct systems providing critical services, SBC, CER, LAN elements, and endpoints. All VVoIP system devices including voice endpoints and portions of the LAN that directly support one or more special-C2 users must be minimally provided 8 hours UPS. Document the VVoIP system design with UPS implementation. Note: UPS systems supplying power to infrastructure supporting special-C2 and C2 users must also support environmental power to prevent equipment failures. This support must be commensurate with the users supported (8 or 2 hours as appropriate).
Lavender hyperlinks in small type off to the right (of CSS
class id
, if you view the page source) point to
globally unique URIs for each document and item. Copy the
link location and paste anywhere you need to talk
unambiguously about these things.
You can obtain data about documents and items in other
formats. Simply provide an HTTP header Accept:
text/turtle
or
Accept: application/rdf+xml
.
Powered by sagemincer