Protected Distribution System (PDS) Construction - Hardened Carrier

From Traditional Security

Part of PDS Construction - Hardened Carrier

Associated with IA controls: DCSR-3, PESS-1, ECCT-2

SV-40984r3_rule Protected Distribution System (PDS) Construction - Hardened Carrier

Vulnerability discussion

A PDS that is not constructed and configured as required could result in the undetected interception of classified information.

Check content

Check to ensure data cables are installed in a carrier configured as a "Hardened Carrier". The carrier must be constructed of electrical metallic tubing (EMT), ferrous conduit or pipe, or rigid-sheet steel ducting, utilizing elbows, couplings, nipples, and connectors of the same material. NOTE: A Modular PDS may be used if constructed of solid metal components - as described above.

Fix text

Data cables must be installed in a carrier configured as a "Hardened Carrier" IAW NSTISSI 7003. The carrier must be constructed of electrical metallic tubing (EMT), ferrous conduit or pipe, or rigid-sheet steel ducting, utilizing elbows, couplings, nipples, and connectors of the same material. NOTE: A Modular PDS may be used if constructed of solid metal components - as described above.